HEPA Filters, Bag Filters & HEPA Housing

Fabricated using superior quality raw material, our range of HEPA Filters, Bag Filters & HEPA Housing are highly in demand in the global market.

Details:

HEPA FILTERS ( CATS – UK )

S. No.

Items Descriptions

Sizes (mm)

Sizes(Inches)

Air Flow m3/h

1

HEPA FILTERS- CATS -UK

DEEP PLEAT HEPA FILTER GALVANIZE FRAME, ALUMINUM SEPARATORS
EFFICIENCY : 99.997%
CLASS : H13
INITIAL PRESSURE DROP: 250pa

610 x 610 x 292

24 * 24 * 12

2200

305 x 305 x 292

12 * 12 * 12

550

610 x 610 x 150

24 * 24 * 06

1100

305 x 305 x 150

12 * 12 * 06

275

457 x 457 x 150

18 * 18 * 06

560

457 x 457 x 292

18 * 18 * 12

1120

2

HEPA FILTERS- CATS -UK

MINI PLEAT HEPA FILTER H14 EXTRUDED ALUMINUM FRAME, HOT MELT BEADS
EFFICIENCY : 99.999%
CLASS : H14
INITIAL PRESSURE DROP: 200pa

610 x 610 x 69

24 * 24 * 03

1000

305 x 305 x 69

12 * 12 * 03

250

915 x 610 x 69

36 * 24 * 03

1500

457 x 457 x 69

18 * 18 * 03

564

610 x 1220 x 69

24 * 48 * 03

1000

Bottom/Top Loading, Side/Top Connection Type, SS, GI/CRCA Powder coated construction, Slab/False ceilin Mounted.

  • Combines all the essential functions required for pharmaceutical and biotechnology facilities
  • Controls and connections accessible from room side
  • Fully welded seams
  • Quick filter change
  • Capability to isolate the room during filter change
Application:

Turbulent airflow clean rooms in pharmaceutical and bio-pharma.

Type:

Terminal filter ducted ceiling exhaust housing for HEPA/ULPA filters in clean rooms, gel seal, with individual bubble tight damper.

Construction:

1.6mm aluminium, continuously welded. Or G.I. 1.6 mm

Duct connection:

Rectangle, Round, fully welded ribbed inlet on top and side

Damper:

Individual adjustable bubble tight damper for airflow adjustment and hood bubble tight isolation.

Included functions:

Static pressure port.

Damper control with damper position indicator.
Overall efficiency test: downstream sample port.

Ports:

Chrome-plates brass quick disconnect.

For filters:

MEGALAM HFU H14 or U15 gel seal MD, MX and MG depth.

Filter seal:

Immediate airtight seal by knife edge technology and gel seal filters.

Filter mounting:

Quick filter change by pre-positioned rotating clamps.

Controls:

Individual MPPS scanning, EN 1822 individual test report in the box.

Fastening:

Suspended or fixed by 4 hanging pads.

Grille:

Stainless steel 304 flush perforated hinged grilles, 40% open with 38mm removable trim.

Scroll to Top